Outdoor units

Panasonic air conditioner outdoor unit PACi standard PZ U-125PZ2E8 12.5kW 400V R32

Order No.: 758.2219
Manufacturer number: U-125PZ2E8
Manufacturer: Panasonic

To previous product 758.1238
To subsequent product 758.2289

Loading

One click to the most important information:

Description

High-quality technology and an attractive design make PACi Standard an ideal solution for demanding applications where operating efficiency is important. The compact design a low weight makes these units suitable for smaller commercial and private applications where space is limited. These ...

High-quality technology and an attractive design make PACi Standard an ideal solution for demanding applications where operating efficiency is important. The compact design a low weight makes these units suitable for smaller commercial and private applications where space is limited. These outdoor units are significantly more compact than previous models and their low weight makes them suitable for use in a wide range of different locations. 

After successfully switching its entire range of home air conditioners to use the environmentally friendly refrigerant R32, Panasonic is now also doing the same with its PACi outdoor units for commercial systems. The PACi models in the Elite range have power ratings from 3.6 to 14.0 kW. The PACi models in the Standard range have power ratings from 6.0 to 14.0 kW.

Benefits of R32:
• Easy to install, easy to use
• Minimal negative environmental affects
• Saves energy and reduces costs
• Small dimensions

show more


Features

  • Compact outdoor units, just one fan up to 14 kW
  • Good balance between system cost and energy efficiency
  • Excellent ESEER/SCOP values for this device category with standard inverter.
  • SEER: A++ / SCOP: A+ with 10.0 kW device combined with 4-way cassette
  • Can be combined with all regulation and control ...
  • Compact outdoor units, just one fan up to 14 kW
  • Good balance between system cost and energy efficiency
  • Excellent ESEER/SCOP values for this device category with standard inverter.
  • SEER: A++ / SCOP: A+ with 10.0 kW device combined with 4-way cassette
  • Can be combined with all regulation and control options for ECOi
  • Can be used in dual systems

show more


Suitable products
Indoor unit - ceiling suspended unit
Panasonic air conditioner PACi ceiling PT S-125PT2E5B 12.5kW

Panasonic air conditioner PACi ceiling PT S-125PT2E5B 12.5kW

Order No.: 758.2188
Indoor unit - concealed duct unit
Panasonic air conditioner PACi concealed duct unit PF S-125PF1E5B 12.5kW

Panasonic air conditioner PACi concealed duct unit PF S-125PF1E5B 12.5kW

Order No.: 758.2196

Accessories / Replacement parts

  • Other accessories
    Panasonic inverter board HIC PACi U-100PZ2E8 400V HIC
    Order No.: 758.2760
  • Weatherproof hood
    Panasonic air conditioner accessories PACi PAW-WPH3-A weatherproof hood U100-140PZ
    Order No.: 758.2645

Technical data

Dimensions
Width
980 mm
Height
996 mm
Depth
370 mm
General information
Connectable indoor units
3
Kältemittel­einsatzbereich
R32
Amount of refrigerant
2,98 kg
max. height difference
indoor unit/outdoor unit
30 / 15 m
max. pre-filled line length
30 m
zul. Leitungslänge
(min. - max.)
5 - 50 m
permissible filling quantity per meter
45
g/m
Electrical Data
Nominal operating current (Cooling/Heating)
5,20 / 4,15 A
Supply voltage
400/3/50 V/Ph/Hz
max. power consumption
10 A
Weight
Weight net
94 kg
Performance data
Design load
Heating
12,50 kW
at -10 °C
Cooling
12,50 kW
Air volume
Heating (high)
4680 m³/h
Cooling (high)
5160 m³/h
Nominal heating capacity
12,50 kW
Nominal cooling capacity
12,5 kW
Nominal power consumption
Heating
3,21 kW
Cooling
3,76 kW
SCOP
3,75
SEER
5,75
Pipe connections
Liquid line
9,52 mm
3/8 inch
Suction gas line
15,88 mm
5/8 inch
Sound data
Sound pressure level
Heating (high)
55 dB(A)
explanation 4
Cooling (high)
55 dB(A)
explanation 4
Sound power
Heating (high)
73 dB(A)
Cooling (high)
73 dB(A)
Temperature data
Air temperature
Heating
-15 bis +24 °C
Cooling
-10 bis +43 °C

Notes

  1. EER/COP values are calculated based on EN14511.
  2. SEER/SCOP values are calculated according to EU Regulation 626/2011 for models with a rated power up to 12 kW and EU Regulation 2281/2016 for models with a rated power above 12 kW.
  3. The annual power consumption is calculated based on the specifications in EU Regulation 626/2011.
  4. Measurement locations - indoor unit: 1 m in front of and 1 m below the unit. The measured values are based on EUROVENT document 6/C/006-97.
  5. Outdoor unit placed higher than indoor unit. * A fuse of 3 A is recommended for the indoor unit.
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading

Login now for complete access

To login