Indoor units

Panasonic air conditioner split wall PKEA CS-E15PKEA 4.2KW server air-con

Order No.: 758.1118
Manufacturer number: .
Manufacturer: Panasonic

To subsequent product 758.2143

Loading

One click to the most important information:

Description

Cooling rooms containing electronics is particularly important where: The air conditioning devices used for cooling have to be reliable and also provide the necessary cooling capacity when outdoor temperatures are very low. Environmental aspects must also not be overlooked. The PKEA ...

Cooling rooms containing electronics is particularly important where: The air conditioning devices used for cooling have to be reliable and also provide the necessary cooling capacity when outdoor temperatures are very low. Environmental aspects must also not be overlooked. The PKEA wall-mounted inverter air conditioning units from Panasonic thoroughly meet these requirements.

Separately available interface accessory for controlling the climate in IT rooms
PAW-SERVER-PKEA: Redundancy control interface and switchover on fault for 2 PKEA interior units in IT rooms, fault alerts via isolated contacts.

show more


Features

  • Year round cooling mode operation down to -15 °C
  • Optimum effectiveness even with very low outdoor temperatures
  • Low resistance anti-friction bearing
  • Additional pipe temperature sensor for frost protection
  • The devices can be used with existing R22 refrigerant lines
  • Option to integrate the devices ...
  • Year round cooling mode operation down to -15 °C
  • Optimum effectiveness even with very low outdoor temperatures
  • Low resistance anti-friction bearing
  • Additional pipe temperature sensor for frost protection
  • The devices can be used with existing R22 refrigerant lines
  • Option to integrate the devices into the Panasonic P-Link communication bus for VRF and PACi devices using P-Link adapter CZ-CAPRA1

show more


Suitable products
Outdoor unit
Panasonic air conditioner outdoor unit split PKEA CU-E15PKEA 4.2KW Professional R410A

Panasonic air conditioner outdoor unit split PKEA CU-E15PKEA 4.2KW Professional R410A

Order No.: 758.1218

Accessories / Replacement parts

  • Communication
    Panasonic communication system RAC CZ-CAPRA1 operation & fault message
    Order No.: 758.1801
  • Control via internet
    Panasonic communication system PA-AC-WIFI-1 control p. internet D3,B4,
    Order No.: 758.1785
  • Redundancy circuit
    Panasonic redundancy server PAW-SERVER-PKEA f. IT-rooms
    Order No.: 758.1714
  • Remote controls
    Panasonic RAC remote control wired CWA75C3375 CS-ExxPKEA
    Order No.: 758.2751

Technical data

Dimensions
Width
870 mm
Height
295 mm
Depth
255 mm
Electrical Data
Recommended overcurrent relay
16 A
Nennbetriebsstrom
Heizen
6,5 A
Kühlen
5,4 A
Connection cable
4 x 1,5 mm²
Supply voltage
230/1/50 V/Ph/Hz
max. power consumption
9,6 A
Weight
Weight net
10 kg
Performance data
Dehumidification
2,4 l/h
Air volume
Heating (high)
900 m³/h
Cooling (high)
846 m³/h
Nominal heating capacity
5,40 kW
explanation 2
Nominal cooling capacity
4,20 kW
Nominal power consumption
Heating
1,44 kW
Cooling
1,20 kW
Sound data
Schalldruckpegel
Heizen
(Niedrig/Mittel/Hoch)
29 / 35 / 43 dB(A)
explanation 3
Kühlen
(Niedrig/Mittel/Hoch)
29 / 32 / 43 dB(A)
explanation 3
Sound power
Heating (high)
59 dB(A)
Cooling (high)
59 dB(A)

Notes
1) At an outdoor temperature of 30 °C and a room temperature of 19.5 °C WB.
2) The annual power consumption is based on the standards ErP Directive.
3) Measurement locations: Indoor unit: 1 m in front of and 80 cm below the unit; outdoor unit: 1 m in front of the device at a height of 1.5 m. The measured values are based on EUROVENT document 6/C/006-97.
4) 70 mm need to be added for pipe connections.
5) Energy efficiency scale from A+++ to D.

Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.