- Products
- Danfoss outdoor unit Optyma Plus OP-MPUC162MLP00E 114X4433
Reciprocating piston
Danfoss outdoor unit Optyma Plus OP-MPUC162MLP00E 114X4433
Icon. Image similar to product.
Icon. Image similar to product.
Technical data
General information
Type
MPUC162MLP00E 400V
Electrical Data
Starting current (locked rotor)
140 A
Wiring diagram
SP3
Supply voltage
400/3/50 V/Ph/Hz
max. operating current
25,0 A
max. operating current
Fan
2,2 A total
Performance data
Refrigerating capacity
19827 W
refrigerant=R 404A, ambient temperature=32 °C, evaporating temperature=-5 °C
19827 W
refrigerant=R 507A, ambient temperature=32 °C, evaporating temperature=-5 °C
23108 W
refrigerant=R 404A, ambient temperature=32 °C, evaporating temperature=0 °C
23108 W
refrigerant=R 507A, ambient temperature=32 °C, evaporating temperature=0 °C
26754 W
refrigerant=R 404A, ambient temperature=32 °C, evaporating temperature=-5 °C
26754 W
refrigerant=R 507A, ambient temperature=32 °C, evaporating temperature=5 °C
30791 W
refrigerant=R 404A, ambient temperature=32 °C, evaporating temperature=10 °C
30791 W
refrigerant=R 507A, ambient temperature=32 °C, evaporating temperature=10 °C
10486 W
refrigerant=R 404A, ambient temperature=38 °C, evaporating temperature=-20 °C
10486 W
refrigerant=R 507A, ambient temperature=38 °C, evaporating temperature=-20 °C
12524 W
refrigerant=R 404A, ambient temperature=38 °C, evaporating temperature=-15 °C
12524 W
refrigerant=R 507A, ambient temperature
Collector data
Collector volume
13,6 l
Sound data
Sound pressure level
47 dB(A)
Fan data
Power consumption
260 W
Air throughput
12200 m³/h
Number of fans
2 pcs
Compressor data
Built-in compressor
MLZ076
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Recently viewed products
Loading
Login now for complete access
To login
Loading