Extreme efficiency, quality, compact – the ECOi EX series, which uses R32 refrigerant, has been expanded to minimise the environmental impact of VRF systems in decarbonised buildings. The advanced R32 technology and optid design make it a sustainable alternative to R410A. With a lower GWP and ...

Extreme efficiency, quality, compact – the ECOi EX series, which uses R32 refrigerant, has been expanded to minimise the environmental impact of VRF systems in decarbonised buildings. The advanced R32 technology and optid design make it a sustainable alternative to R410A. With a lower GWP and superior efficiency, it ensures sustainability throughout its entire service life.

show more


Features

  • Scalability up to 36 PS in multi-combination systems
  • optional safety measures for the refrigerant
  • reliable quality
  • flexible installation options
  • all modules fitted with Bluefin heat exchangers

Accessories / Replacement parts

  • Wärmerückgewinnungsbox
    Panasonic ECOi Zubehör 3-Leiter-Wärmerückgew. m.Sicherheitsv.
    Order No.: 758.3814
  • Panasonic ECOi Zubehör 3-Leiter-Wärmerückgewinnungsbox
    Order No.: 758.3815

Technical data

Dimensions
Width
880 mm
Height
1660 mm
Depth
765 mm
General information
Application
Kühlen und Heizen
Type
VRF
Construction
Außengerät
Refrigerant
R32
Electrical Data
Supply voltage
400/3/50 V/Ph/Hz
Performance data
Air volume
205 m³/h
Nominal heating capacity
31,5 kW
Nominal cooling capacity
28,0 kW
Nominal power consumption
Heating
7,49 kW
Cooling
7,92 kW
Pipe connections
Liquid line
3/8 Zoll
9,52 mm
 
1/2 Zoll
12,70 mm
 
Erläuterung 1
Hot gas line
3/4 Zoll
19,05 mm
 
7/8 Zoll
22,22 mm
Suction gas line
5/8 Zoll
15,88 mm
 
3/4 Zoll
19,05 mm
 
Erläuterung 1
Sound data
Sound pressure level
Heating VRF AU
61,0 dB(A)
Cooling VRF AU
61,0 dB(A)
Flüsterbetrieb bis 50 dB(A)
Sound power level
Heating
78,0 dB(A)
Cooling
78,0 dB(A)
Temperature data
max. Operating
+52 °C
Kühlen
 
+18 °C
Heizen
min. operating temperature
-10 °C
Kühlen
 
-20 °C
Heizen

Erläuterungen

  1. Gleichwertige Leitungslänge bis zum weitesten Innengerät kürzer 100 m / länger 100 m (wenn die gleichwertige Länge des längsten Strangs 100 m überschreitet, muss sowohl für die Sauggas- als auch die Flüssigkeitsleitung der nächst größere Leitungsdurchmesser gewählt werden).
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information. Discounts are rounded without decimal places.