Technical data
General information
Type
MPUC068MLP00E
Electrical Data
Starting current (locked rotor)
60 A
Wiring diagram
SP3
Supply voltage
400/3/50 V/Ph/Hz
max. operating current
13,0 A
max. operating current
Fan
1,1 A total
Performance data
Flow volume
12 m³/h
Refrigerating capacity
4829 W
refrigerant=R 404A, ambient temperature=32°C, evaporation temperature=-20 °C
4829 W
refrigerant=R 507A, ambient temperature=32°C, evaporation temperature=-20 °C
5887 W
refrigerant=R 404A, ambient temperature=32°C, evaporation temperature=-15 °C
5887 W
refrigerant=R 507A, ambient temperature=32°C, evaporation temperature=-15 °C
7094 W
refrigerant=R 404A, ambient temperature=32°C, evaporation temperature=-10 °C
7094 W
refrigerant=R 507A, ambient temperature=32°C, evaporation temperature=-10 °C
8458 W
refrigerant=R 404A, ambient temperature=32°C, evaporation temperature=-5 °C
8458 W
refrigerant=R 507A, ambient temperature=32°C, evaporation temperature=-5 °C
9979 W
refrigerant=R 404A, ambient temperature=32°C, evaporation temperature=0 °C
9979 W
refrigerant=R 507A, ambient temperature=32°C, evaporation temperature=0 °C
11661 W
refrigerant=R 404A, ambient temperature=32°C, evaporation temperature=5 °C
11661 W
refrigerant=R 507A, ambient temperature=32°C
Collector data
Collector volume
7,6 l
Sound data
Sound pressure level
40 dB(A)
Fan data
Power consumption
130 W
Air throughput
6100 m³/h
Number of fans
1 pcs
Compressor data
Built-in compressor
MLZ030