- Products
- Refrigeration components
- System components
- Filter dryers/KM filters
- Intake pipe filter dryer/housing
- Sporlan cleaning dryer C-609-S-T-HH 1-1/8" solder
Intake pipe filter dryer/housing
Sporlan cleaning dryer C-609-S-T-HH 1-1/8" solder
Icon. Image similar to product.
Order No.: 251.350024
Manufacturer number: 401839
Manufacturer: Sporlan / PARKER
More in this category: Intake pipe filter dryer/housing
One click to the most important information:
Description
Burnout filters for intake and fluid lines ensure circuits are properly decontaminated and cleared of moisture, dirt, acids and wax deposits. Catch-All® burnout filters use a special combination of a molecular sieve, activated alumina and activated charcoal in cast inserts together with a ...?xml>
Burnout filters for intake and fluid lines ensure circuits are properly decontaminated and cleared of moisture, dirt, acids and wax deposits. Catch-All® burnout filters use a special combination of a molecular sieve, activated alumina and activated charcoal in cast inserts together with a highly efficient filter. Catch-All® burnout filters are intended for temporary use only.
Features
- Filtration: 20 micrometres
- Can be used with HFCs, CFCs
- Pressure Equipment Directive 2014/68/EU compliant
- REACH 2006/1907/EC compliant
Technische Daten
Sauggastemperatur | -40 bis +66 | °C |
Technical data
Dimensions
Diameter
76 mm
Total length
406 mm
Length
358 mm
General information
Version
1-1/8" Inch
Construction
Löt
Type
C-609-S
Pressure
max. operating pressure
45 bar
Liquids
Water adsorption
54.5 g
refrigerant=R 134A
65.8 g
refrigerant=R 404A
65.5 g
refrigerant=R 507A
18.9 g
refrigerant=R 407C
17.7 g
refrigerant=R 410A
at 52°C g
Weight
Weight net
2,7 kg
Performance data
Flow power
93.0 kW
refrigerant=R 134A
106.0 kW
refrigerant=R 407C
67.0 kW
refrigerant=R 404A
67.0 kW
refrigerant=R 507A
106.0 kW
refrigerant=R 410A
11.9 kW
refrigerant=R 134A
15.4 kW
refrigerant=R 407C
12.8 kW
refrigerant=R 404A
12.8 kW
refrigerant=R 507A
19.9 kW
refrigerant=R 410A
pressure loss 0.07 bar kW
Pipe connections
Outlet
1 1/8 Zoll
Inlet
1 1/8 Zoll
Temperature data
suction gas temperature
-40 bis +66 °C
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading
Loading