Evaporating pressure regulators

Danfoss evaporator pressure regulator KVP35 solder 034L0032

Order No.: 226.0497
Manufacturer number: 034L0032
Manufacturer: Danfoss

More in this category: Evaporating pressure regulators

Loading

One click to the most important information:

Description

The KVP is installed in the intake line behind the evaporator. Its purpose:

1. To maintain a constant evaporating pressure and thus a constant surface temperature in the evaporator. Modulating regulation. Throttling the intake line adjusts the refrigerant volume to the load on the ...

The KVP is installed in the intake line behind the evaporator. Its purpose:

1. To maintain a constant evaporating pressure and thus a constant surface temperature in the evaporator. Modulating regulation. Throttling the intake line adjusts the refrigerant volume to the load on the evaporator. 

2. Protection against the evaporating pressure being too low (e.g. to protect against freezing in a water cooler). The regulator closes if the pressure in the evaporator drops below the set value.

3. Differentiation of the evaporating pressure in a refrigeration system with a compress and several evaporators with different evaporating temperatures.

show more


Features

  • Precise, adjustable pressure regulation

  • Wide power spectrum and range of applications

  • Vibration suppression

  • Compact angled design for easy installation in any position

  • “Hermetically” hard soldered design

  • Available in many sizes and flanged and ODF solder versions

  • For R 22, R 134a, R 404A, R ...

  • Precise, adjustable pressure regulation

  • Wide power spectrum and range of applications

  • Vibration suppression

  • Compact angled design for easy installation in any position

  • “Hermetically” hard soldered design

  • Available in many sizes and flanged and ODF solder versions

  • For R 22, R 134a, R 404A, R 12, R 502 and or fluorinated refrigerants

  • Regulation range: ±0 to +5.5 bar

  • Max. temperature: 100 °C

  • Approved operating pressure: 18 bar

show more


Technical data

Performance data
Nominal capacity
6.1 kW
refrigerant=R 134A
 
7.7 kW
refrigerant=R 404A
 
7.7 kW
refrigerant=R 507A
 
7.9 kW
refrigerant=R 407C
Pipe connections
Solder
13/8 inch"
inch
 
35
mm

1) Die Nennleistung ist die Leistung des Reglers bei Verdampfungstemperatur t0=-10 °C, Verfüssigungstemperatur tK=+25 °C, Druckabfall im Regler Dp=0,2 bar, Offset=0,6 bar.

2) KVP wird ohne Überwurfmuttern geliefert. Seperate Überwurfmuttern können geliefert werden.

Die Anschlussgröße darf nicht zu klein gewählt werden, da Gasgeschwindigkeiten über 40 m/s in den Stutzen des Reglers Strömungsgeräusche erzeugen können.

Die Leistungstabelle finden Sie unter "Downloads" im PDF.

Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.

Customers also bought...

Loading

Login now for complete access

To login
Article in stock