Capacity controllers

Danfoss hot gas distributor LG16-28 069G4003

Order No.: 226.0423
Manufacturer number: 069G4003
Manufacturer: Danfoss

More in this category: Capacity controllers

One click to the most important information:

Description

The CPCE is a power regulator for adjusting compressor power to the actual evaporator load. The CPCE is installed into a bypass between the low and high pressure sides of a refrigeration system. It is specially design for guiding hot gas between the evaporator and the thermostatic expansion ...

The CPCE is a power regulator for adjusting compressor power to the actual evaporator load. The CPCE is installed into a bypass between the low and high pressure sides of a refrigeration system. It is specially design for guiding hot gas between the evaporator and the thermostatic expansion valve. Injection should be done using a type LG hot gas mixer.





Dimensioning and power

The following data about the refrigeration system is required when selecting a CPCE power regulator:

  • Refrigerant

  • Min. intake gas temperature tS

  • Compressor power PV at min. intake gas temperature

  • Min. evaporator power Q0

  • Condensation temperature tk

The regulator power can then be calculated at the compressor power minus the evaporator power at the minimum intake gas temperature and condensation temperature. The LG hot gas mixer is measured after the connection adapters.

The power is a result of a reduction in the intake pressure / the intake gas temperature by DtS = 4K. The specific intake gas temperatures are minimum values, i.e. values after reduction. The specified performance is made up of the hot gas power of the CPCE regulator and the additional power from the thermostatic expansion valve that maintains constant superheating across the evaporator.

show more


Features

  • Outstanding control precision
  • Direct connection to the intake line regulates the passage of hot gas independently of pressure reductions in the evaporator

  • The LG guarantees a homogenous mixture of liquid and gas refrigerants in the evaporator

  • Can be used with R 22, R 134a, R 404A, R507, R407C and ...

  • Outstanding control precision
  • Direct connection to the intake line regulates the passage of hot gas independently of pressure reductions in the evaporator

  • The LG guarantees a homogenous mixture of liquid and gas refrigerants in the evaporator

  • Can be used with R 22, R 134a, R 404A, R507, R407C and other fluorinated refrigerants

  • Introducing hot gas into the evaporator improves the transport of oil to the compressor

  • Protection against too low evaporating temperatures, i.e. it prevents the evaporator from icing up

  • LG can be used on its own for mixing hot gas during hot gas defrosting

  • Control range: 0 to 6 bar

  • Maximum temperature of medium: 140 °C

  • Approved operating pressure: 21.5 bar

  • Maximum design pressure: 28 bar

show more


Technical data

Pipe connections
Expansion valve
Solder
1 1/8"
inch
 
28
mm
Liquid distributor
Solder
1 1/8"
inch
 
28
mm
Hot gas
Solder
5/8"
inch
 
16
mm
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading

Login now for complete access

To login
Article in stock