Electronic

Danfoss Colibri expansion valve electr. ETS 50C 28x28mm with sight glass 034G7702

Order No.: 231.040359
Manufacturer number: 034G7702
Manufacturer: Danfoss

To previous product 231.0524

More in this category: Electronic

One click to the most important information:

Description

ETS Colibri stepper motor valves are electronically operated expansion valves for precise superheat control.
These electronic expansion valves can also be operated as biflow valves in reversible systems. (E.g. heat pump applications) The ETS Colibri
ETS 12.5C - 100C valves replace the former ...

ETS Colibri stepper motor valves are electronically operated expansion valves for precise superheat control.
These electronic expansion valves can also be operated as biflow valves in reversible systems. (E.g. heat pump applications) The ETS Colibri
ETS 12.5C - 100C valves replace the former series ETS 12.5B - ETS 100B.

show more


Features

• Fastest expansion valve with stepper motor technology current available (one stroke 0-100% approx. 3’)
• For all refrigerants (except R717 and R744) including R290, R1234ze, R1234yf...
• Can be controlled by Danfoss superheat controllers (EKE1A/B/C, EKD316C) with adaptive ...

• Fastest expansion valve with stepper motor technology current available (one stroke 0-100% approx. 3’)
• For all refrigerants (except R717 and R744) including R290, R1234ze, R1234yf...
• Can be controlled by Danfoss superheat controllers (EKE1A/B/C, EKD316C) with adaptive superheat regulation
• Fully hermetic valve with stainless steel body and bimetal connections
• Integrated inspection glass, ETS-C 25 and up
• Simple dimensioning using Coolselector II

show more


Accessories / Replacement parts

  • Connection cable
    Danfoss connection cable for ETS M12 2m 034G7073
    Order No.: 231.040350
  • Danfoss connection cable for ETS M12 8m 034G7074
    Order No.: 231.040351

Technical data

General information
Number of sight glasses
1
Pressure
max. operating pressure
50 bar
Performance data
Throughput
KV value
2,50 m³/h
Nominal capacity
239.0 kW
R134a to=-10 °C
 
211.5 kW
R404A/ R507A to=-10°
 
202.6 kW
R404A/R507A to=-30°C
 
317.3 kW
R407C to=-30°
 
346.3 kW
R410A t0=+5°C
 
299.0 kW
R448A/ R449A to=-10°C
 
291.9 kW
R448A/ R449A to=-30°
 
231.0 kW
R452A to=-10°C
Pipe connections
Outlet
Solder
28 mm
ODF
 
1 1/8 inch
ODF
Inlet
Solder
28 mm
ODF
 
1 1/8 inch
ODF
Temperature data
Media temperature
-40 bis +70 °C
Ambient temperature
-40 bis +70 °C

Rated power specified in kW for a condensation temperature tc=40 °C, supercooling tcu=0K, dew point

Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.

Customers also bought...

Loading

Login now for complete access

To login
Available in another country - please contact your local office