Technical data

General information
Fin spacing
4,0 mm
Type
DHN 401 N EC
Electric defrosting
Block
4x 350 W
Total
1400 W
Electrical Data
Power consumption
Fan
0,73 A
Supply voltage
230/1/50 V/Ph/Hz
Surfaces
Surface
15,3 m²
Weight
Weight net
35 kg
Performance data
Nominal capacity
4.90 kW
temperature difference=10 °K, evaporating temperature=0 °C
 
3.26 kW
temperature difference=8 °K, evaporating temperature=-8 °C
Pipe connections
Outlet
22 mm
Inlet
12* mm
Sound data
Sound pressure level
50 dB(A)
Sound power
68
dB(A)
Fan data
Power
85 W
Air throughput
1930 m³/h
Number of fans
1x 350 pcs
Fan speed
1115 rpm-1
Fan type
S3G EC 350 S
Throw distance
2x 9 m
Volume
Pipe volume
3,4 dm³
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.