Reciprocating piston

Tecumseh Außeneinheit Silensys Inverter SILFHV4544Z-TX 400V

Order No.: 106.4065
Manufacturer number: SH74030244
Manufacturer: Tecumseh / L'Unite

To previous product 106.4055

More in this category: Reciprocating piston

One click to the most important information:

Description

This frequency-regulated version has been developed based upon the new Tecumseh Silensys condensing units. Design changes have brought further improvements to the noise produced by this new generation of condensing unit as well as a reduction in power consumption. Frequency regulation means ...

This frequency-regulated version has been developed based upon the new Tecumseh Silensys condensing units. Design changes have brought further improvements to the noise produced by this new generation of condensing unit as well as a reduction in power consumption. Frequency regulation means that these devices can now also be used in refrigerating systems with variable cooling requirements. The frequency converter operates independently on the intake pressure and modifies the speed to optimally adapt performance to the current cooling requirements. These devices therefore represent a cost-effective and energy-efficient alternative to conventional multi-compressor power rack systems.

• Optimally adjusts compressor power to the load on the system
• Proven quality and excellent noise emission vales of the Tecumseh Silensys along with the functionality of a reliable and simple to operate frequency converter
• Energy savings resulting from better performance adjustment in optimal evaporating temperatures

show more


Accessories / Replacement parts

  • Bedieneinheit
    L'Unite control unit f. Silensys M, L, XL
    Order No.: 106.3894
  • Condenser
    L'Unite condenser CDS 2N SILENSYS V2/3 (S,M,L) 8338279
    Order No.: 106.2662
  • Crankcase heater
    L'unite oil sump heater 230V 9-HT5-24 27W for SILENSYS 8583036
    Order No.: 106.3758
  • Frequency inverter
    L'Unite frequency converter for SILAGV4546ZTZ
    Order No.: 106.3961
  • Tecumseh Frequenzumformer Ersatz 8580161 für Silensys Inverter
    Order No.: 106.4808
  • Junction box set
    L'Unite junction box kit Junior 8627015
    Order No.: 106.3707
  • Liquid collector
    L'Unite liquid collector without burst protection RSV 3,90L without shut-off valves 8380159
    Order No.: 106.1751
  • L'Unite liquid collector without burst protection RSV 6,00L without shut-off valves 8380160
    Order No.: 106.1752
  • Netzfilter
    Tecumseh Netzfilter Filter FS23639-30-07
    Order No.: 106.4811
  • Refrigerator oil
    L'Unite refrigeration oil polyester oil can 1L 8685030
    Order No.: 531.0601
  • Speed regulator
    L'Unite speed controller R404A SILENSYS M/L/XL EC motor 8580088
    Order No.: 106.3746
  • Umbau-Kit
    L'Unite conversion kit 8664150
    Order No.: 106.4307
  • Ventilator unit
    L'Unite fan unit SILENSYS VTL 450mm 230V EC 8551139
    Order No.: 106.3948
  • Ventilsatz
    L'Unite valve set suction f. TAG4534/43/46/53 7/8 A solder 8683014
    Order No.: 106.3989

Technical data

Dimensions
Art der Aufstellung
Außenaufstellung
General information
Type
vollhermetisch
Expansion
V
see explanation 1
Refrigerant
R404A
 
R507A
 
R448A
 
R449A
 
R452A
Motor version
TRI
Type
SIL FHV4544Z-TX
Condensation type
luftgekühlt
Electrical Data
Start-up current
43,0 A
nominal current
7,5 A
Supply voltage
400/3/50 V/Ph/Hz
max. operating current
13,1 A
Weight
Weight net
97,00 kg
Performance data
Frequency controlled
Ja
Displacement volume
68,00 cm³
Pipe connections
Liquid line
10,00 mm
3/8 Zoll
Löt
siehe Erläuterung 2
Suction line
22,00 mm
7/8 Zoll
Löt
siehe Erläuterung 2
Collector data
Collector volume
3,90 l
Sound data
Sound power level
68,0 dB(A)
Fan data
Diameter
450 mm
Power
90 W
Air throughput
2970 m³/h
Number of fans
1 pcs
Compressor data
Built-in compressor
FH4544Z-TX

Erläuterung

  1. Expansion: C = Kapillarrohr; V = Expansionsventil
  2. Metrische Werte sind gerundet
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.