Technical data
General information
Type
MPUC125MLP00E 400V
Electrical Data
Starting current (locked rotor)
95 A
Wiring diagram
SP3
Supply voltage
400/3/50 V/Ph/Hz
max. operating current
20,0 A
max. operating current
Fan
2,2 A total
Performance data
Refrigerating capacity
9674 W
refrigerant=R 404A, ambient temperature=27 °C, evaporating temperature=-20 °C
9674 W
refrigerant=R 507A, ambient temperature=27 °C, evaporating temperature=-20 °C
11981 W
refrigerant=R 404A, ambient temperature=27 °C, evaporating temperature=-15 °C
11981 W
refrigerant=R 507A, ambient temperature=27 °C, evaporating temperature=-15 °C
14595 W
refrigerant=R 404A, ambient temperature=27 °C, evaporating temperature=-10 °C
14595 W
refrigerant=R 507A, ambient temperature=27 °C, evaporating temperature=-10 °C
14512 W
refrigerant=R 404A, ambient temperature=27 °C, evaporating temperature=-5 °C
14512 W
refrigerant=R 507A, ambient temperature=27 °C, evaporating temperature=-5 °C
20721 W
refrigerant=R 404A, ambient temperature=27 °C, evaporating temperature=0 °C
20721 W
refrigerant=R 507A, ambient temperature=27 °C, evaporating temperature=0 °C
24205 W
refrigerant=R 404A, ambient temperature=27 °C, evaporating temperature=5 °C
24205 W
refrigerant=R 507A, ambient tempera
Collector data
Collector volume
13,6 l
Sound data
Sound pressure level
47 dB(A)
Fan data
Power consumption
260 W
Air throughput
12200 m³/h
Number of fans
2 pcs
Compressor data
Built-in compressor
MLZ058
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.