- Produkte
- Bitzer semi-hermetic Condensing unit NEW ECO LH33/2HES-1Y 400V/3/50Hz
Semi-hermetic
Bitzer semi-hermetic Condensing unit NEW ECO LH33/2HES-1Y 400V/3/50Hz
Icon. Image similar to product.
Accessories / Replacement parts
-
Crankcase heater
-
Motor protection
-
Speed regulator
-
Weatherproof housing
Technical data
General information
Option larger collector
FS56
Type
LH33/2HES-1Y
Electrical Data
Power consumption
1.90 kW
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=0 °C
1.67 kW
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-5 °C
1.47 kW
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-10 °C
1.28 kW
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-15 °C
1.11 kW
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-20 °C
0.95 kW
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-25 °C
0.81 kW
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-30 °C
0.67 kW
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-35°C
0.55 kW
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-40 °C
1.10 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=10 °C
1.02 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=5 °C
0.95 kW
refrigerant=R 134A, ambient temperature=27
Power consumption
Fan
0,55 A
Supply voltage
400/3/50 V/Ph/Hz
max. operating current
3,8 A
Weight
Weight net
71 kg
Performance data
Refrigerating capacity
4710 W
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=0 °C
4020 W
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-5 °C
3370 W
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-10 °C
2790 W
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-15 °C
2260 W
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-20 °C
1790 W
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-25 °C
1380 W
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-30 °C
1030 W
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-35 °C
725 W
refrigerant=R 407F, ambient temperature=27 °C, evaporating temperature=-40 °C
4480 W
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=10 °C
3800 W
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=5 °C
3170 W
refrigerant=R 134A, ambient temperature=27 °
Pipe connections
Liquid line
3/8
inch
10
mm
3/8
inch
Suction line
5/8
inch
16
mm
5/8
inch
Collector data
Collector type
FS36
max. refrigerant charge
3.3 kg
refrigerant=R 134A
2.9 kg
refrigerant=R 404A
Fan data
Power consumption
120 W
Air throughput
1710 m³/h
Compressor data
Compressor type
2HES-1Y
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.