Reciprocating piston

Bock compressor HAX 4/650-4 400V

Order No.: 102.5105
Manufacturer number: 13789
Manufacturer: Bock

Loading

One click to the most important information:

Description

The new energy-efficient “e” models have 2, 4, 6 or 8 cylinders with capacities of 11.4 to 281 m³/h (50 Hz).
The GEA range of semi-hermetic compressors comprises a complete range of performance options using modern and innovative compressor technologies in a 2, 4, 6 or 8 cylinder ...

The new energy-efficient “e” models have 2, 4, 6 or 8 cylinders with capacities of 11.4 to 281 m³/h (50 Hz).
The GEA range of semi-hermetic compressors comprises a complete range of performance options using modern and innovative compressor technologies in a 2, 4, 6 or 8 cylinder design with capacities ranging from 5.4 to 281 m³/h (50 Hz)
The right solution for all applications.
HG (Hermetic Gas-cooled)
Conventional suction gas-cooled compressor design for air conditioning and normal refrigeration applications
HA (Hermetic Air-cooled)
A special GEA design for achieving very low temperatures (R407F) using an air-cooled motor and direct suction on the cylinder.
Universal
- e.g. R134a, R407C, R407F, R404A/R507A
- a compressor design for all common refrigerants used in air conditioning, normal refrigeration and freezing
- maximum operating pressure: 28 bar

  • excellent cooling performance with minimal energy consumption
  • wide range of applications without requiring any additional cooling
  • wear-resistant and durable drive mechanisms
  • safe and reliable oil supply
  • sturdy valve plate design
  • quiet and low vibration
  • economical power regulation
  • IP65 cabinet for electrical connections
  • GEA Compressor Management INT69 GTML Diagnose
  • INT69G electronic motor protection
  • oil sump heater
  • minimal space requirements

show more


Accessories / Replacement parts

  • Crankcase heater
    Bock oil sump heating-BS 230V replacement 80W f. HA/HG(X)4, AM(X)4/5,F(X)4/5 08425
    Order No.: 102.2834
  • Oil differential pressure sensor
    Bock oil differential pressure sensor 230V DELTA-P II f. HA/G(X) 4-7 HG(X)44e
    Order No.: 102.4912
  • Oil pressure safety switch
    Bock oil differential pressure switch BS 230V MP54 f. HG(X)4-7 HG(X) 44e
    Order No.: 102.4668
  • Oil servicing valve
    Bock oil service valve HA/HG(X)4 mounted
    Order No.: 102.4608
  • Bock oil service valve HA/HG(X)4-8 replacement 07946
    Order No.: 102.4913
  • Refrigerator oil
    Fuchs refrigeration machine oil Reniso Triton SE 55 can 10L
    Order No.: 531.0811
  • Fuchs refrigeration machine oil Reniso Triton SE 55 can 1L
    Order No.: 531.0802
  • Thermal protection thermostat
    Bock thermal protection thermostat HA/HG(X)22+34, 4 till 8
    Order No.: 102.4614
  • Unloaded start system
    Bock start-up relief 230V HA/HG(X)4 AL92 with thermostat wiithout check valve
    Order No.: 102.4605
  • Bock start-up relief BS 230V HA/HG(X)4 AL92 with cylinder cover 08527
    Order No.: 102.4823

Technical data

General information
Number of cylinders
4 pcs
Refrigerant
R404A/R507A
Type
HAX4/650-4
Electrical Data
Starting current (locked rotor)
107 / 140 A
(see explanation 2)
Supply voltage
400/3/50 V/Ph/Hz
(see explanation 2)
max. starting current
140 A
max. operating current
22 A
(see explanation 1)
max. power consumption
11,4 kW
(see explanation 2)
Weight
Weight net
156 kg
Performance data
Flow volume
56,6 m³/h
at 1450 rpm-1
Pipe connections
Pressure line
28 mm
 
1 1/8 inches
Suction line
35 mm
 
1 3/8 inches
Volume
Oil charge
ESTER SE55
Oil quantity
3,4 l

Notes

  1. Max. power consumption values are for 50 Hz operation. Multiply these values by a factor of 1.2 for 60 Hz operation. The max. operating current remains the same.
    - Max. operating current / max. power consumption when selecting
    contactors, leads and fuse contactors: Category AC3.
  2. Tolerance (± 10%) based on the mean voltage range. Other voltages and current types on request
    380-420 V Y/YY - 3 - 50 Hz PW
    440-480 V Y/YY - 3 - 60 Hz PW
    PW = Part Winding, motors for part winding start (no start up reduction required)
    - Wind ratio: HGX(HAX)4, HGX(HAX)5, HGX(HAX)6 = 66% / 33%
    - Y/Δ designs on request.