two pipe system

Mitsubishi air conditioner outdoor unit City Multi R2 PURY-EP350 YNW-A

Mitsubishi Electric Logo
Order No.: 719.4670
Manufacturer number: PURY-EP350YNW-A
Manufacturer: Mitsubishi

To previous product 719.4234
To subsequent product 719.5205

Loading

One click to the most important information:

Description

More than just the sum of its parts
The new Hybrid City Multi-System (HVRF) is the world’s first 2-line system for simultaneous cooling and heating with heat recovery technology that combines the advantages of a direct evaporation system with those of a water-based system. The technology is ...

More than just the sum of its parts
The new Hybrid City Multi-System (HVRF) is the world’s first 2-line system for simultaneous cooling and heating with heat recovery technology that combines the advantages of a direct evaporation system with those of a water-based system. The technology is based on the City Multi R2 heat pump system from Mitsubishi Electric. The HVRF system consists of an R2 outdoor unit from the City Multi series and the new Hybrid BC controller that enables energy to be transferred from the refrigerant to the inner water circuit. The indoor units in the system are fitted with water registers.

Also available with R32
The modern Hybrid VRF systems work with City Multi VRF outdoor units using R32. The combination of a reduced refrigerant capacity and low GWP value lowers the system’s CO2 equivalent rating to below 21% compared to conventional VRF systems using R410A. This is lower than the rate that must be achieved by 2030, stipulated by the F-Gas regulations. Standards compliant installation: The Hybrid VRF technology means you are able to enjoy the benefits of a VRF system and remain in compliance with applicable standards even when using refrigerant R32.


System comparison: Less is more
Planning and installing a 2-line system gives you more flexibility and is significantly easier than installing a cold water unit and an additional heat generator with four lines. For example, City Multi systems require no additional pumps, tanks or reversing valves. 2-line systems have significantly fewer points at which connections must be made, thus reducing potential leaks and making the system more reliable and easier to maintain.

show more


Features

  • Energy-saving heat recovery
  • Highest degree of comfort
  • Simple to install
  • Less planning required
  • Simultaneous heating and cooling

Technical data

Dimensions
Width
1240 mm
Height
1858 mm
Siehe Erläuterung 2
Depth
740 mm
General information
Connectable indoor units
1 - 35
Construction
Außengerät
Refrigerant charge
R410A
Amount of refrigerant
8,0 kg
max. height difference
indoor unit/outdoor unit
50 m
zul. Leitungslänge
(min. - max.)
600 m
Electrical Data
Recommended overcurrent relay
40 A
Nennbetriebsstrom
Heizen
17,2 A
Kühlen
14,8 A
Supply voltage
400/3/50 V/Ph/Hz
Weight
Weight net
279 kg
Performance data
COP
4,39
EER
4,54
Air volume
Heating (high)
15000 m³/h
Cooling (high)
15000 m³/h
Nominal heating capacity
45,00 kW
Nominal cooling capacity
40,00 kW
SCOP
4,1
SEER
8,4
Pipe connections
Liquid line
18 mm
Gas line
28 mm
Sound data
Sound pressure level
Heating (high)
62,5 dB(A)
Siehe Erläuterung 1
Cooling (high)
62,5 dB(A)
Siehe Erläuterung 1

Notes

  1. Sound pressure level measured at a distance of 1 m away from the device and at a height of 1 m.
  2. The height can be reduced to 1,798 mm by removing the feet.
  3. Simple distance


Our air conditioning systems and heat pumps contain fluorinated greenhouses gases R410A, R407C, R134a, R32.
Further information can be found in the respective operating manual.

Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading

Login now for complete access

To login