- Products
- Copeland semi-hermetic condensing unit air-cooled B8-KJ-7X CAG 230V/1/50Hz
Semi-hermetic
Copeland semi-hermetic condensing unit air-cooled B8-KJ-7X CAG 230V/1/50Hz
Icon. Image similar to product.
Technical data
General information
Type
B8-KJ-7X CAG
Oil charge
RL32-3MAF
Electrical Data
Power consumption
0.54 kW
refrigerant=R 404A, ambient temperature=43 °C, evaporating temperature=-45 °C
0.65 kW
refrigerant=R 404A, ambient temperature=43 °C, evaporating temperature=-40 °C
0.76 kW
refrigerant=R 404A, ambient temperature=43 °C, evaporating temperature=-35 °C
0.88 kW
refrigerant=R 404A, ambient temperature=43 °C, evaporating temperature=-30 °C
1.01 kW
refrigerant=R 404A, ambient temperature=43 °C, evaporating temperature=-25 °C
1.15 kW
refrigerant=R 404A, ambient temperature=43 °C, evaporating temperature=-20 °C
0.64 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-20 °C
0.69 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-15 °C
0.75 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-10 °C
0.81 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-5 °C
0.87 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=0 °C
0.94 kW
refrigerant=R 134A, ambient temperature=2
Performance data
Refrigerating capacity
1.37 kW
refrigerant=R 404A, ambient temperature=43 °C, evaporating temperature=-20 °C
1.08 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-20 °C
1.37 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-15 °C
1.71 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-10 °C
2.10 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-5 °C
2.53 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=0 °C
3.00 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=5 °C
3.20 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=7 °C
3.55 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=10 °C
3.85 kW
refrigerant=R 134A, ambient temperature=27 °C, evaporating temperature=-12.5 °C
0.98 kW
refrigerant=R 134A, ambient temperature=32 °C, evaporating temperature=-20 °C
1.26 kW
refrigerant=R 134A, ambient temperature=32 °