Standing units

Arbonia chest unit Condiline DXD 53+1 4-Leiter,1 RR (ZR) wihtout housing IV/IO

Order No.: 778.130376
Manufacturer number: DXD05311200X10A
Manufacturer: Arbonia

One click to the most important information:

Description

Fan coils in the DXD series are ideally suited for use in small to medium hotel rooms and offices. They can be integrated into the false ceilings. The wide range of available accessories means almost all installation options are available to you. The integrated tangential fans allow for low ...

Fan coils in the DXD series are ideally suited for use in small to medium hotel rooms and offices. They can be integrated into the false ceilings. The wide range of available accessories means almost all installation options are available to you. The integrated tangential fans allow for low energy, almost silent operation. Due to the modular concept of the system, the DXD cabinet units with sturdy frame construction are designed for installing inside false ceilings. However, they are also available in an aesthetically pleasing and elegant housing made from white (RAL 9003) coated steel with matching light grey side parts made from plastic.

Condiline DXD cabinet units with tangential fan
This range consists of 6 sizes (from 90 to 945 m3/h) and 5 variants (for wall and ceiling installation, with and without cladding). Each of these variants features 3-line registers that can be extended with an additional register with 1x pipe (4-line system).

All variants can be supplied with integrated heat register. Please ask our technical specialists for performance data.

show more


Features

  • Range of variants for a wide range of different applications
  • Especially quiet models
  • Robust frame construction
  • With or without cladding
  • For wall or ceiling installation
  • Many connection and control options
  • Easy to maintain filter
  • Compact size for installing into false ceilings with a grid size of less ...
  • Range of variants for a wide range of different applications
  • Especially quiet models
  • Robust frame construction
  • With or without cladding
  • For wall or ceiling installation
  • Many connection and control options
  • Easy to maintain filter
  • Compact size for installing into false ceilings with a grid size of less tan 1.25 m
  • Up to 9 design sizes depending on variant
  • Colour: Front RAL 9003, cladding Pantone Cool Grey 1C (light grey)
  • AC or EC motor technology
  • With tangential fan
  • Two or three way valves
  • Two or four line systems
  • Important information about the technical data:
  • Acoustic pressure level: In a 100m3 space, reverberation period of 0.5 s, spatial damping factor 9 dB(A)
  • Acoustic power level: According to Eurovent
  • Air inlet temperature: +27 °C, relative humidity: 50%
  • Correction coefficients for other relative humidity values:
    • 46%: Total cooling capacity: 0.90
    • 46%: Sensitive cooling capacity: 1.00
    • 48%: Total cooling capacity: 0.95
    • 48%: Sensitive cooling capacity: 1.00
  • Water temperature: °C, inlet 7 - outlet 12

show more


Technical data

Dimensions
Width
992 mm
Height
530 mm
without feet
 
630 mm
with feet
Depth
218 mm
Performance data
Drehzahlstufe 1
­Wasserdurchfluss
260 l/h
Speed level 1
Pressure loss water
3,4 kPa
Total cooling capacity
1,51 kW
Air volume
215 m³/h
Sound pressure level
17 dB(A)
Sound power level
26 dB(A)
Sensitive cooling capacity
1,04 kW
Speed level 2
Pressure loss water
4,9 kPa
Total cooling capacity
1,85 kW
Air volume
275 m³/h
Sound pressure level
22 dB(A)
Sound power level
31 dB(A)
Sensitive cooling capacity
1,28 kW
Drehzahlstufe 2
Wasserdurchfluss
318 l/h
Speed level 3
Pressure loss water
6,9 kPa
Total cooling capacity
2,25 kW
Air volume
345 m³/h
Sound pressure level
28 dB(A)
Sound power level
37 dB(A)
Sensitive cooling capacity
1,57 kW
Drehzahlstufe 3
Wasserdurchfluss
387 l/h
Speed level 4
Pressure loss water
9,1 kPa
Total cooling capacity
2,62 kW
Air volume
420 m³/h
Sound pressure level
32 dB(A)
Sound power level
41 dB(A)
Sensitive cooling capacity
1,85 kW
Drehzahlstufe 4
Wasserdurchfluss
451 l/h
Speed level 5
Pressure loss water
10,6 kPa
Total cooling capacity
2,87 kW
Air volume
475 m³/h
Sound pressure level
34 dB(A)
Sound power level
43 dB(A)
Sensitive cooling capacity
2,04 kW
Drehzahlstufe 5
Wasserdurchfluss
494 l/h
Speed level 6
Pressure loss water
13,9 kPa
Total cooling capacity
3,34 kW
Air volume
580 m³/h
Sound pressure level
39 dB(A)
Sound power level
48 dB(A)
Sensitive cooling capacity
2,40 kW
Drehzahlstufe 6
Wasserdurchfluss
574 l/h
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.