two pipe system

Mitsubishi air conditioner outdoor unit City Multi PUHY-RP550 YSJM

Mitsubishi Electric Logo
Order No.: 719.4214
Manufacturer number: PUHY-RP550 YSJM
Manufacturer: Mitsubishi

Loading

One click to the most important information:

Description

Mitsubishi Electric has developed the Replace Multi outdoor units, with which it is possible for the first time to continue using the existing pipe network despite a change from R22 to R410A refrigerant when replacing air conditioning units. With our patented Replace technology the decision in ...

Mitsubishi Electric has developed the Replace Multi outdoor units, with which it is possible for the first time to continue using the existing pipe network despite a change from R22 to R410A refrigerant when replacing air conditioning units. With our patented Replace technology the decision in favour of highly efficient air conditioning systems with R410A can be made more easily because the necessary investment is significantly reduced compared to additional replacement of the piping system. Various methods enabling the reuse of piping are available for the room air conditioners, multi-split systems or VRF systems. It can also be used in air conditioning systems in which third-party products have previously been used and devices from Mitsubishi Electric are now being newly installed.

show more


Features

• Reuse of the existing pipe network
• Large performance range: 22.4 to 113.0 kW cooling / heating performance
• Compact design with a depth of only 760 mm
• Long cable routes up to 300 m
• Low sound pressure level from 56 dB(A)
• High COPs up to 5.21 (PUHY-RP850YSJM-A)
• ...

• Reuse of the existing pipe network
• Large performance range: 22.4 to 113.0 kW cooling / heating performance
• Compact design with a depth of only 760 mm
• Long cable routes up to 300 m
• Low sound pressure level from 56 dB(A)
• High COPs up to 5.21 (PUHY-RP850YSJM-A)
• All indoor units of the City Multi VRF series can be combined
• Up to 32 indoor units can be connected to one outdoor unit

show more


Accessories / Replacement parts

  • Required distributor set
    Mitsubishi City Multi distributor set CMY-RP100 VBK f. 2xPUHY-RP
    Order No.: 719.2454

Technical data

Dimensions
Width
1870 mm
Height
1710 mm
Depth
760 mm
General information
Connectable indoor units
1 - 32
Application
Kühlen und Heizen
Amount of refrigerant
18,0 kg
max. height difference
indoor unit/outdoor unit
50 m
zul. Leitungslänge
(min. - max.)
300 m
Electrical Data
Nennbetriebsstrom
Heizen
29,8 A
Kühlen
31,3 A
Supply voltage
400/3/50 V/Ph/Hz
Weight
Weight net
510,0 kg
Performance data
Air volume
Heating (high)
22200 m³/h
Cooling (high)
22200 m³/h
Nominal power consumption
Heating
16,6 kW
Cooling
17,5 kW
Pipe connections
Liquid line
16 mm
Gas line
35 mm
Sound data
Sound pressure level
Heating VRF AU
61,0 dB(A)
Cooling VRF AU
61,0 dB(A)
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.