two pipe system

Mitsubishi air conditioner outdoor unit City Multi PUHY-HP200 YHM-A Zubadan

Mitsubishi Electric Logo
Order No.: 719.3243
Manufacturer number: PUHY-HP200 YHM-A
Manufacturer: Mitsubishi

More in this category: two pipe system

Loading

One click to the most important information:

Description

The R2 series has been developed for promote energy-saving and environmentally friendly systems for use in modern buildings. The R2 series is the world’s only heat recovery system that allows simultaneous heating and cooling with just two pipes. The central components in each R2 system is ...

The R2 series has been developed for promote energy-saving and environmentally friendly systems for use in modern buildings. The R2 series is the world’s only heat recovery system that allows simultaneous heating and cooling with just two pipes. The central components in each R2 system is the BC controller - a refrigerant distributor that forms a single refrigeration and control unit with the outdoor device and thus enable heat recovery to take place. The BC controller allows up to 50 indoor units to be connection with one outdoor unit with just two pipelines.

show more


Features

  • Each indoor unit can operate independently in either heating or cooling mode
  • Heat recovery up to 100%
  • No refrigerant distributor required

Scope of delivery

  • 1x Mitsubishi Klima Außengerät City Multi PUHY-HP200 YHM-A Zubadan

Technical data

Dimensions
Width
920 mm
Height
1710 mm
Depth
760 mm
General information
Connectable indoor units
1 - 17
Construction
Außengerät
Refrigerant charge
R410A
Amount of refrigerant
9,00 kg
max. height difference
indoor unit/outdoor unit
50 m
zul. Leitungslänge
(min. - max.)
300 m
Electrical Data
Recommended overcurrent relay
32 A
Nennbetriebsstrom
Heizen
10,40 A
Kühlen
10,20 A
Supply voltage
400/3/50 V/Ph/Hz
Weight
Weight net
220 kg
Performance data
COP
3,83
EER
3,5
Nominal heating capacity
25,00 kW
Nominal cooling capacity
22,40 kW
Pipe connections
Liquid line
12 mm
Gas line
18 mm
Sound data
Sound pressure level
Heating (high)
56 dB(A)
explanation 1
Cooling (high)
56 dB(A)
explanation 1