Description

The Slim air cooler from Güntner is designed for small and low cold stores with limited space. Its narrow design allows for space-saving installation. The unit is easy to assemble and the entire tray unit, including the inner drip tray, can be folded down for cleaning. All materials used are ...

The Slim air cooler from Güntner is designed for small and low cold stores with limited space. Its narrow design allows for space-saving installation. The unit is easy to assemble and the entire tray unit, including the inner drip tray, can be folded down for cleaning. All materials used are approved for use in the food industry.

The unit comes standard with a powder-coated aluminium housing for corrosion protection. The coating protects the entire fin block evenly against corrosion.

show more


Features

  • Drain according to DIN ISO 228-1 with G thread
  • Casing: AlMG - powder-coated RAL 9003
  • Empty weight: 18 kg
  • Aluminium fins
  • Number of hangers: 4

Technical data

General information
Defrost heating
ja
Type
Deckenflachverdampfer
Refrigerant
R1234yf
Fin spacing
7 mm
Pipe volume
2 l
Electrical Data
Supply voltage
Fan
230/1/50 V/Ph/Hz
Performance data
Nominal capacity
1,9 kW
t0=-8°C, DT1=8K, R1234yf (TP)
Pipe connections
Outlet
18 mm
Inlet
16 mm
Sound data
Sound pressure level
33,9 dB(A)
in 3 m (Erläuterung 1)
Fan data
Number of fans
1 pcs
Throw distance
8 m
(Erläuterung 2)

Explanations

  • According to the envelope method in accordance with EN 13487/EN 9614-1, tolerance = +2 dB(A). Applies only to AC fans, AC fans with sine wave controllers and EC fans. Noise caused by other control methods or water spray systems, as well as sound reflections occurring at the installation site, are not taken into account and may lead to increased sound pressure levels.
  • Distance at which an air velocity of 0.5 m/s can still be measured isothermally in an ideal room. The achievable penetration depth of the air flow into the cold room depends on the room geometry and other factors.