Warning systems

Bacharach gas warning device IP66 w. sensor MGS-410 propan 6302-0064

Order No.: 476.3773
Manufacturer number: 6302-0064
Manufacturer: Bacharach

One click to the most important information:

Description

The MGS-410 refrigerant gas detector is intended for use in cold storage rooms and can be used alone, in combination with the MGS-408 controller or in combination with the BMS/BAS of the facility concerned. It conforms with refrigerant safety regulations (ASHRAE 15 and EN 378) and features an ...

The MGS-410 refrigerant gas detector is intended for use in cold storage rooms and can be used alone, in combination with the MGS-408 controller or in combination with the BMS/BAS of the facility concerned. It conforms with refrigerant safety regulations (ASHRAE 15 and EN 378) and features an audible and visible alarm signal to alert staff of a refrigerant leak.

show more


Accessories / Replacement parts

  • Control unit
    Bacharach control unit 8-channel MGS-408 f. MGS410/50/60
    Order No.: 476.3861
  • Bacharach control unit 2-channel MGS-402 for MGS410
    Order No.: 476.3887
  • Externes Netzteil
    Bacharach Spannungsversorgung MGS 24V 40W für MGS-400 Serie
    Order No.: 476.3896

Technical data

Dimensions
Width
130 mm
Installation height
height:
0-2000 m AMSL
Height
130 mm
Length
68 mm
General information
Alarm output
int. alarm tone
72 dB at 10 cm
 
alarm delay
configurable (0 to 15 minutes)
Display
indicators:
multicoloured status-LED
 
internal alarm tone 72 dB at 10 cm
Housing
material:
ABS
 
protection:
IP41 or IP66
Pressure
Operating pressure
pressure:
23.6 to 32.5"Hg (800 to 1,100 mbar)
Electrical Data
Output analog
analogue output:
4 to 20 mA, 0 to 5 V, 0 to 10 V, 1 to 5 V (standard) or 2 to 10 V
Input
inputs:
keys (×2),
 
magnetic switch (×2)
Connections
Bluetooth®:
Bluetooth® Low Energy, BLE 4.2
 
Modbus:
 
Connection:
connector block RS-485
 
baud rate:
9600 (standard) or 19200
 
data bits
8
 
parity:
none (standard), even or uneven
 
stop bits:
1 (standard) or 2
 
repetition interval:
500 ms (minimum)
Connection cable
Cable (mains):
2-lead, 16 - 28 AWG
 
Cable (relay):
2-lead, 16 - 28 AWG
 
Cable (Modbus):
recommended: Belden 3106A (or equivalent), 3-lead, double twisted pair + earth, shielded cable with 120 ? characteristic impedance, 16 - 28 AWG
Supply voltage
power source: V/Ph/Hz
19.5 bis 28.5 V DC or 24 V AC ±20%; 4 W
Humidity
Relative humidity
humidity:
5 to 90 % relative humidity, non-condensing
Weight
Weight net
260 g
Temperature data
Operating range
temperature: °C
semiconductor: -40 to 50 °C electrochemical: varies according to gas type and/or concentration, see MGS-400 (Art.-Nr. 1100-2294) operating instructions for the full temperature range list.
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.
Loading

Login now for complete access

To login