Air-cooled

Emicon reversible Heat pump LRi 10 HE/LX/RV with inverter 230V

Order No.: 775.6021
Manufacturer number: .
Manufacturer: Emicon

One click to the most important information:

Description

The highly efficient LRi heat pump has been specially developed for use in connection with underfloor heating and for applications where maximum heating efficiency is required. Units are optimised for heating. They produce hot water temperatures up to 58 °C and work best in ambient ...

The highly efficient LRi heat pump has been specially developed for use in connection with underfloor heating and for applications where maximum heating efficiency is required. Units are optimised for heating. They produce hot water temperatures up to 58 °C and work best in ambient temperatures of -20 °C and below. The LRi version functions as a service water heater. They activate an external three-way valve. All models are delivered reversible as standard and can therefore also be used for cooling.

show more


Scope of delivery

• Flow monitors,
• Speed-controlled AC fans,
• Evaporator frost protection heating,
• High and low pressure manometers,
• Single pump with inverter


Ausführung


Technical data

Dimensions
Width
1047 mm
Height
913 mm
Depth
465 mm
General information
Energy efficiency­class
Heating
A++
explanation 2
Refrigerant charge
R410A
Electrical Data
Start-up current
22,4 A
Supply voltage
230/1/50 V/Ph/Hz
max. operating current
14,5 A
Weight
Circa
95,5 kg
Performance data
Nominal heating capacity
7,35 kW
explanation 1
Nominal cooling capacity
5,30 kW
explanation 3
Nominal power consumption
Heating
2,20 kW
explanation 1
Cooling
2,40 kW
explanation 3
SCOP
4,24
explanation 2
Sound data
Sound pressure level
32 dB(A)
explanation 5
Sound power
63 dB(A)
explanation 4

Notes:

  1. Heating: Outdoor temperature 7 °C DB / 6 °C WB; water temperature 30/35 °C
  2. Average conditions, variable - reg EU 811/2013
  3. Cooling: Outdoor temperature 35 °C; water temperature 12/7 °C
  4. Acoustic pressure level according ISO 3744
  5. Acoustic pressure level measured at 10 m free field distance according to ISO 3744 (LS version)
Technical modifications reserved. Product images may differ from the actual product and are meant for demonstration purposes only. Absolutely no liability can be assumed for possible indication errors and errors in the manufacturers’ information.